SI45F
Download Specifications in .pdf format
Photon counter
Counter SI45F is used in high-speed fire-extinguishing and alarm systems, as well as in burner flame control devices.
Main characteristics
Working voltage |
V |
280 |
Working voltage range |
V |
250 ÷ 300 |
Own background |
count / s |
1,0 max |
Sensitivity to flame of stearin candle (at a distance of 1m) |
count / s |
12 min |
Sensitivity to bulbs light (10000 lux) |
count / s |
2,0 max |
Sensitivity to diffused sunlight (50000 lux) |
count / s |
3,0 max |
Sensitivity to light of headlights (5000 lux) |
count / s |
3,0 max |
Sensitivity to light of fluorescent lamps (1000 lux) |
count / s |
3,0 max |
Angle of view from the dome |
degrees |
90 |
Reduction of sensitivity within the viewing angle |
% |
35 max |
Life expectancy |
hour |
10000 |
Weight |
g |
40 |
Overall dimensions
Application conditions
The photon counter is designed for use with the schemes of extinction, satisfying the following requirements:
Working voltage | V | 280 |
Working voltage range | V | 250 ÷ 300 |
The time of the discharge combustion in the counter | μs | 30 max |
Limiting pulse repetition frequency | count / s | 25 |
Average current through the counter at a speed of accounts 25 count / s | μА | 0,1 max |
Residual voltage at the counter in the period of extinction | V | 50 ÷ 120 |